Maximum continuous operating voltage

3×340 to 530 VAC

Nominal operating voltage

3×380 to 480 VAC

Rated currents

4 to 1100 A @ 40°C

Overload capability

2 x rated current at switch on for 30 seconds

1.5 x rated current for 1 minute, once per hour

Typical dv/dt reduction

≥factor 5

Impedance (Uk)

0.8% @ 400 VAC, 50 Hz and rated current

Motor frequency

0 to 60 Hz

Motor cable length

30 m Max. @ 16 kHz

Switching frequency

fPWM 2 to 16 kHz

High potential test voltage

P –> E 3000 VAC for 3 sec
P –> P 3000 VAC for 3 sec

Overvoltage category

OV III (IEC 60664-1)

Temperature range (operation and storage)

-25°C to +100°C (25/100/21) operation and storage

Protection category

IP 00 (KL types according to VBG 4)

Flammability corresponding to

UL 94 V-2

Design corresponding to

EN 61558-2-20 (VDE 0570-2-20), UL 508C, CSA C22.2 NO. 14

Insulation class

UL electrical insulation system JL-180

Lifetime (calculated)

20 years