Maximum continuous operating voltage

3×340 to 530 VAC

Nominal operating voltage

3×380 to 480 VAC

Rated currents

4.5 to 1200 A

Overload capability

1.5× rated current for 1 minute, once per hour

Residual ripple voltage

<5%

Impedance (Uk)

6% @ 400 V, 50 Hz and rated current

Motor frequency

0…60 Hz (up to 200Hz with derating, see user manual)

Motor cable length

Up to 1’000 m or 2’000 m (see user manual)

Switching frequency

fPWM Min. 2 or 4kHz, max. 16kHz, see filter selection table

High potential test voltage

P –> E 2500 VAC, 60s

Overvoltage category

OV III (IEC 60664-1)

Pollution degree

PD3

Temperature range (operation and storage)

-40°C to +45°C fully operation
+45°C to +100°C (up to 18A) or +70°C (26A and above) derated operation
-40°C to +70°C transport and storage

Climatic category

40/070/21

Cooling

Natural cooling AN

Protection category

IP 00,IP 20

Design corresponding to

Filter: UL 61800-5-1, EN 61800-5-1
Chokes:EN 61558-2-20 or EN 60076-6

MTBF (Mil-HB-217F)

>500,000 h @ 40°C/480 V